[. . . ] INSTALLATION INSTRUCTIONS
CAUTION: Turn off power to the electric service or panel and to equipment to be protected
before installing any Surge Protection Device. All wiring should be done by a qualified electrician and comply with the National Electric Code and local electric codes.
INSTALLATION
1. Test and verify system voltage to assure proper model selection of Surge Protection Device (SPD). [. . . ] Make sure that the phase wires have the correct voltage level between them. Note that for the 240 volt High Leg Delta, the wire lead for the High Leg is colored RED, and must be connected to the phase that measures approximately 208 volts to neutral and to ground. Failure to comply with this instruction will result in failure of the SPD and void the warranty. If remote monitoring is used, remove the ½" knockout and connect wire leads to the terminal strip located in the monitoring section of the PanelGuard cabinet. Be sure to comply with local and national wiring codes for the voltage of the monitoring circuit. Observe the suggested torque values published by the manufacturer when circuit breakers or separate disconnect devices are used. Close and secure the hinged cover using the locking bolts provided with the cover. Make sure that each Protection Status indicator on the PanelGuard is ON. If not, turn power off and recheck each installation step listed above. If not, turn power off and recheck each installation step listed above. For troubleshooting assistance, call Intermatic at 800-391-4555.
4. 18.
19.
WIRING CONFIGURATIONS
120 VAC Single Phase
Transformer Secondary Load Center or equipment L1 Black
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
PanelGuard
Line to Neutral Line to Ground
120 120
N G
White
Green
Use of Circuit Breakers is optional
120/240 VAC Single (Split) Phase
Transformer Secondary
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
Load Center or equipment
L1 L2 N G Black Black White Green
PanelGuard
Line to Line Line to Neutral Line to Ground
240 120 120
Use of Circuit Breakers is optional
120/208 VAC Three Phase WYE
Transformer Secondary
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
Load Center or equipment
L1 Black L2 Black L3 Black N G White Green
PanelGuard
Line to Line Line to Neutral Line to Ground
208 120 120
Use of Circuit Breakers is optional
120/240 VAC Three Phase Delta High Leg Delta
Transformer Secondary
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
Load Center or equipment
L1 Black L2 Red L3 Black N White G Green
PanelGuard
Line to Line Line to Neutral High Leg to Neutral Line to Ground High Leg to Ground
240 120 208 120 208
Use of Circuit Breakers is optional
277/480 VAC Three Phase WYE
Transformer Secondary
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
Load Center or equipment
L1 Black L2 Black L3 Black N G White Green
PanelGuard
Line to Line Line to Neutral Line to Ground
480 277 277
Use of Circuit Breakers is optional
480 VAC Three Phase DELTA
Transformer Secondary
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
Load Center or equipment
L1 L2 L3 Black Black Black Green
PanelGuard
Line to Line Line to Ground
480 480
G
Use of Circuit Breakers is optional
Alarm relay for remote monitoring
Violet n/c Brown - c
PanelGuard
Common - Brown Normally Open - orange Normally Closed - Violet
Orange n/o
Normal operating condition relay energized
Violet n/c Brown - c Orange n/o
AC lead connections
Alarm relay connections
Alarm condition relay not energized
Contact your Intermatic Representative or Distributor for information on other hardwired panel Surge Protection Devices. Discover the convenience of integral fusing and the versatility of replaceable protection modules in Intermatic's full line of Surge Protection Devices.
TEN YEAR LIMITED PRODUCT WARRANTY For
PanelGuardTM2000 SURGE PROTECTION DEVICES
(1) What Is Covered By This Limited Warranty
Repair or Replacement of Product Intermatic Incorporated ("Intermatic") warrants to the original purchaser only, the Intermatic PanelGuard 2000 Series Surge Protection Device(s) shall be free from defects in material or workmanship for a period of ten years from date of purchase. If the purchaser discovers a defect in material or workmanship, the purchaser must promptly submit a warranty claim. Upon a determination by Intermatic that the Product is defective, Intermatic shall correct any defect in material or workmanship by, at Intermatic's option, either repairing or replacing the Defective Product. Any repair, including both parts and labor, shall be at Intermatic's expense. [. . . ] Some states do not allow limits on warranties or on remedies for breach in certain transactions. In such states, the limits in this paragraph and in paragraph (3) may not apply.
(5) Time Limit for Bringing Suit
No action arising out of any claimed breach of warranty may be brought more than one year after the cause of action has accrued.
(6) No Other Warranties
Unless modified in a writing signed by both parties, this agreement is understood to be the complete and exclusive agreement between the parties, superseding all prior agreements, oral or written, and all other communications between the parties relating to the subject matter of this agreement. No employee of Intermatic or any other party is authorized to make any warranty in additional to those made in this agreement.
INTERMATIC INCORPORATED
SPRING GROVE ILLINOIS 815-675-2321 Fax: 815-675-2112 http://www. intermatic. com
158EG10423 PDF 8. 02 [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE INTERMATIC PG2000
Click on "Download the user Manual" at the end of this Contract if you accept its terms, the downloading of the manual INTERMATIC PG2000 will begin.